| Parameters | Units | About | Contact | |||||||||
| + | 1 reference(s) hidden. |
| Honeywell Field Solutions | TWC9000 | 0201 | Resource |
| Description: | AI 6 |
| Parent: | DIAGNOSIS_BLK |
| Category: | Vendor |
| Access: | View Only |
| Type: | Enumeration |
| Help: | reason for OUT.status not Good, bits at BLK_ERR and other diagnosis |
| Enumerations: | 0 – Startup Device 1 – RB: MODE_BLK.ACTUAL is OOS 8 – Memory failure 32 – no schedule 33 – period of execution 34 – period of execution to large 48 – MODE_BLK.PERMITTED doesn't include Auto 49 – MODE_BLK.TARGET is set OOS 50 – MODE_BLK.TARGET is set MAN 51 – MODE_BLK.ACTUAL is MAN; Startup to Auto 128 – CHANNEL is uninitialized 129 – UNIT of CHANNEL selected TB.prim_val not convertible to XD UNIT 130 – XD_SCALE: difference between EU_100 and EU_0 is to less 131 – OUT_SCALE: difference between EU_100 and EU_0 is to less 132 – L_TYPE is uninitialized 133 – L_TYPE is direct, XD_SCALE is not equal OUT_SCALE 160 – SIMULATE_STATUS is not Good, Simulation is active 161 – SIMULATE_STATUS limitted, STATUS_OPTS is set, Simulation active 162 – Simulation is active 176 – Transducer Block MODE_BLK.ACTUAL is OOS 177 – CHANNEL selected TB.prim_val.status is Bad 178 – TB.prim_val.status is limitted, STATUS_OPTS is set 179 – CHANNEL selected TB.prim_val.status is Uncertain 192 – OUT.value exceeds OUT_SCALE 240 – unknown reason 255 – ok |