Parameter:
+1 reference(s) hidden.
Honeywell Field SolutionsTWC90000201Resource
Description:AI 6
Parent:DIAGNOSIS_BLK
Category:Vendor
Access:View Only
Type:Enumeration
Help:reason for OUT.status not Good, bits at BLK_ERR and other diagnosis
Enumerations:0 – Startup Device
1 – RB: MODE_BLK.ACTUAL is OOS
8 – Memory failure
32 – no schedule
33 – period of execution
34 – period of execution to large
48 – MODE_BLK.PERMITTED doesn't include Auto
49 – MODE_BLK.TARGET is set OOS
50 – MODE_BLK.TARGET is set MAN
51 – MODE_BLK.ACTUAL is MAN; Startup to Auto
128 – CHANNEL is uninitialized
129 – UNIT of CHANNEL selected TB.prim_val not convertible to XD UNIT
130 – XD_SCALE: difference between EU_100 and EU_0 is to less
131 – OUT_SCALE: difference between EU_100 and EU_0 is to less
132 – L_TYPE is uninitialized
133 – L_TYPE is direct, XD_SCALE is not equal OUT_SCALE
160 – SIMULATE_STATUS is not Good, Simulation is active
161 – SIMULATE_STATUS limitted, STATUS_OPTS is set, Simulation active
162 – Simulation is active
176 – Transducer Block MODE_BLK.ACTUAL is OOS
177 – CHANNEL selected TB.prim_val.status is Bad
178 – TB.prim_val.status is limitted, STATUS_OPTS is set
179 – CHANNEL selected TB.prim_val.status is Uncertain
192 – OUT.value exceeds OUT_SCALE
240 – unknown reason
255 – ok