| Siemens AG | SIPART PS2 FF | 0101 | Analog Output | Transducer |
| Description: | Alarm function (AFCT) |
| Category: | Vendor |
| Access: | Engineer |
| Type: | Enumeration |
| Help: | The drive can report the exceeding (Max.) or dropping below (Min) of a specified stroke or angle of rotation. The response of the alarms (limit contacts) is related to the MPOS scaling (see 'Feedback normalization (YNRM)'. The alarms are reported by the alarm module. The direction of action of the alarm can be set to high active (e.g. 'Alarm 1: Min, Alarm 2: Max') or Low active (e.g. 'Alarm 1: /Min, Alarm 2: /Max'). |
| Enumerations: | 0 – Off, Without function 1 – MI: MA (Alarm 1: Min, Alarm 2: Max) 2 – MI: MI (Alarm 1: Min, Alarm 2: Min) 3 – MA: MA (Alarm 1: Max, Alarm 2: Max) 4 – /MI:/MA (Alarm 1: /Min, Alarm 2: /Max - inverted) 5 – /MI:/MI (Alarm 1: /Min, Alarm 2: /Min - inverted) 6 – /MA:/MA (Alarm 1: /Max, Alarm 2: /Max - inverted) |