Foundation Fieldbus Parameter Search (βeta)

"Taking the frustration out of foundation"

Parameters Units About Contact
 
Parameter:
+1 reference(s) hidden.
Yokogawa Electric CorporationDigital YEWFLO0104DYFTransducer
Description:Alarm Perform
Size:2
Category:Vendor
Access:Engineer
Type:bit Array
Help:The function which clears alarm temporarily. Alarm is cleared by writing 0 to each bit.High vibration output can be selected. (0:0% 1:No action)
Enumerations:0 – Fluctuating (AL-54)
1 – Clogging (AL-53)
2 – Excessive vibration (AL-52)
3 – Transient excessive vibration (AL-51)
4 – Input circuit failure (AL-06)
5 – Flow sensor failure (AL-05)
6 – High vibration output select (0:0%, 1:No action)
8 – PID (Mode, Simulate, schedule)
9 – DI2 (Mode, Simulate, schedule)
10 – DI1 (Mode, Simulate, schedule)
11 – AI2 (Mode, Simulate, schedule)
12 – AI1 (Mode, Simulate, schedule)

+1 reference(s) hidden.
Yokogawa Electric CorporationROTAMASS / RCCT30102ROTAMASSTransducer
Description:Alarm Perform
Size:2
Category:Vendor
Access:Engineer
Type:bit Array
Help:Clear alarm temporarily by writing 0 to each bit.
Enumerations:0 – AI1 operate
1 – AI2 operate
2 – AI3 operate
3 – AI4 operate
4 – AI5 operate
5 – AI6 operate
6 – IT1 operate
7 – IT2 operate
8 – PID operate