Foundation Fieldbus Parameter Search (βeta)

"Taking the frustration out of foundation"

Parameters Units About Contact
 
Parameter:
+2 reference(s) hidden.
Emerson Process ManagementRosemount 5400 Series0203Transducer
Rosemount 5600 TankRadar PRO0103Transducer
Description:Still Pipe Diameter
Unit:RADAR_LEVEL_RANGE.UNITS_INDEX
Category:Vendor
Access:Engineer
Type:32 bit Float
Help:Enter the pipe inner diameter if the antenna is mounted in a still pipe application.

+1 reference(s) hidden.
Emerson Process ManagementRosemount 5600 TankRadar PRO0201Transducer
Description:Still Pipe Diameter
Unit:RADAR_LEVEL_RANGE.UNITS_INDEX
Category:Vendor
Access:Engineer
Type:32 bit Float
Help:Enter the inner pipe diameter for the pipe or bypass well in which the antenna is mounted. This option is only available for pipe antennas and User Defined antennas.The Pipe Inner Diameter is used to compensate for the lower microwave propagation speed inside the pipe. An incorrect value will give a scale factor error.Note: If you have a User Defined antenna which is not mounted in a still pipe or bypass well make sure the Pipe Inner Diameter is set to a value less than or equal to zero (<=0). A value less than or equal to zero means that no correction for pipe is made.