Foundation Fieldbus Parameter Search (βeta)

"Taking the frustration out of foundation"

Parameters Units About Contact
 
Parameter:
+1 reference(s) hidden.
ABB Automation Products GmbHTB82PH0101TB82PH pH, ORP, pIONTransducer
Description:Asymmetric Potential
Minimum Range:-1999
Maximum Range:1999
Category:Vendor
Access:Engineer
Type:16 bit Integer
Help:The Asymmetric Potential value is the electrical potential across the measuring and reference half-cell of the sensor at the isopotential point.When PH_SENSOR_TYPE is Glass or Antimony, Asymmetric Potential is READ_ONLY.Asymmetric Potential can be modified only for Custom pH sensor type.