Foundation Fieldbus Parameter Search (βeta)

"Taking the frustration out of foundation"

Parameters Units About Contact
 
Parameter:
+2 reference(s) hidden.
Emerson Process ManagementRosemount Analytical Oxymitter 50000303Transducer
0401Transducer
Description:Cal constant
Minimum Range:-20
Maximum Range:20
Category:Vendor
Access:View Only
Type:32 bit Float
Help:This parameter represents the constant (offset) value used in the calculation of converting the sensor voltage to an O2 value. The value of this parameter may be manually entered or calculated during a sensor calibration.