Foundation Fieldbus Parameter Search (βeta)

"Taking the frustration out of foundation"

Parameters Units About Contact
 
Parameter:
CAL_STATE_1 CAL_STATE_2 CAL_STATE_STEP CAL_STATE_TIME

+2 reference(s) hidden.
Emerson Process ManagementRosemount Analytical Oxymitter 50000303Transducer
0401Transducer
Description:Cal cycle state
Category:Vendor
Access:View Only
Type:Enumeration
Help:This parameter represents the present state the calibration cycle is in
Enumerations:0 – Normal System Operation
1 – Calibration Required
2 – Apply Test Gas 1
3 – Test Gas 1 Flow
4 – Test Gas 1 Read
5 – Test Gas 1 Done
6 – Apply Test Gas 2
7 – Test Gas 2 Flow
8 – Test Gas 2 Read
9 – Test Gas 2 Done
10 – Abort/Fail
11 – Stop Gas
12 – Purge

+1 reference(s) hidden.
Emerson Process ManagementRosemount 5400 Series0201Transducer
Description:Cal State
Category:Vendor
Access:View Only
Type:Enumeration
Help:The current state of the calibration cycle.
Enumerations:0 – Idle
1 – Apply O2 Low Gas*
2 – Flow O2 Low Gas
3 – Read O2 Low Gas
4 – Apply O2 High Gas*
5 – Flow O2 High Gas
6 – Read O2 High Gas
7 – Apply Comb Low Gas*
8 – Flow Comb Low Gas
9 – Read Comb Low Gas
10 – Apply Comb High Gas*
11 – Flow Comb High Gas
12 – Read Comb High Gas
13 – Stop Gas*
14 – Purge
15 – Arort