Foundation Fieldbus Parameter Search (βeta)

"Taking the frustration out of foundation"

Parameters Units About Contact
 
Parameter:
+2 reference(s) hidden.
Metso AutomationND9000F0301Transducer
0401Transducer
Minimum Range:0
Maximum Range:100
Category:Vendor
Access:Engineer
Type:32 bit Float
Help:Polynomial characterization is described by the formula. f(x)=x/(S+x*(1-S)), where x is the input value and S is the polynominal factor S=1, linear transfer function 0<S<1, function implements quick opening S>1, function implements equal percentage characterization curve