| Parameters | Units | About | Contact | |||||||||
| + | 1 reference(s) hidden. |
| Siemens AG | SIPART PS2 FF | 0101 | Analog Output | Transducer |
| Description: | Setpoint function (SFCT) |
| Category: | Vendor |
| Access: | Engineer |
| Type: | Enumeration |
| Help: | Non-linear valve characteristics can be linearized with this function and any flow characteristics simulated in linear valve characteristics. The 'LINEAR' setting means that the linearization is switched off. The entry of individual setpoint vertex points is only possible in the 'FREE (user-defined)' setting. |
| Enumerations: | 0 – Linear 1 – Equal percentage 1:25 2 – Equal percentage 1:33 3 – Equal percentage 1:50 4 – Equal percentage inverse 25:1 (n1:25) 5 – Equal percentage inverse 33:1 (n1:33) 6 – Equal percentage inverse 50:1 (n1:50) 7 – Free (user defined) |