ALARM_STATE CLEAR_CYCLE_COUNT CLEAR_CYCLE_COUNT2 CYCLE_COUNT2 CYCLE_COUNTER CYCLE_COUNT_ALM CYCLE_COUNT_ALRT_PT CYCLE_COUNT_DB CYCLE_COUNT_LIM CYCLE_COUNT_LIMIT CYCLE_COUNT_PRI LIMIT_CYCLE_COUNT SUB_CODE TIME_STAMP TOTAL_CYCLE_COUNT UNACKNOWLEDGED VALUE VALVE_CYCLE_COUNT

+3 reference(s) hidden.
Tyco Valves & ControlsAVID ZR-F0302Analog InputFunction
Westlock ControlsFPAC-ESD0101Analog InputFunction
0301Analog InputFunction
Category:Vendor
Access:View Only
Type:32 bit Float
Help:Count of number of cycles since last reset.

+1 reference(s) hidden.
Emerson Process ManagementFisher DVC6200f / DVC6000f0203Transducer
Description:Cycle Counter
Category:Vendor
Access:Engineer
Type:32 bit Unsigned Integer
Help:Records the number of times the travel changes direction. The change in direction must occur after the deadband has been exceeded before it can be counted as a cycle. Reset the Cycle Counter by entering zero.

+1 reference(s) hidden.
Foxboro-EckardtSRD 9600902Flowserve Valve PositionerTransducer
Category:Vendor
Access:Engineer
Type:32 bit Unsigned Integer
Help:Cycle counter, which counts changes in movement (up/down or right/left)

+1 reference(s) hidden.
TopWorx Inc.SCM-FF0203Analog InputFunction
Category:Vendor
Access:View Only
Type:32 bit Unsigned Integer
Help:Counter that increments each time the valve opens or closes. The counter increments on partial opens or closes as well. This is actually a 1/2 cycle counter.