Foundation Fieldbus Parameter Search (βeta)

"Taking the frustration out of foundation"

Parameters Units About Contact
 
Parameter:
STAT_KENNL_W_DELAY_TIME

+1 reference(s) hidden.
Siemens AGSIPART PS2 FF0101Analog OutputTransducer
Description:Delay Time Setting
Minimum Range:-120
Maximum Range:100
Category:Vendor
Access:Engineer
Type:32 bit Float
Help:The monitoring time for setting the fault messages (in seconds) can be set in this parameter. The initial value is valid in the 'AUTO' mode (value = -120). The position controller must have reached the controlled state within the set time. The corresponding response threshold can be entered in 'LIM'. The fault message output is activated on exceeding the set time in 'TIM'.