| Parameters | Units | About | Contact | |||||||||
| + | 1 reference(s) hidden. |
| Siemens AG | SIPART PS2 FF | 0101 | Analog Output | Transducer |
| Description: | Delay Time Setting |
| Minimum Range: | -120 |
| Maximum Range: | 100 |
| Category: | Vendor |
| Access: | Engineer |
| Type: | 32 bit Float |
| Help: | The monitoring time for setting the fault messages (in seconds) can be set in this parameter. The initial value is valid in the 'AUTO' mode (value = -120). The position controller must have reached the controlled state within the set time. The corresponding response threshold can be entered in 'LIM'. The fault message output is activated on exceeding the set time in 'TIM'. |