| Parameters | Units | About | Contact | |||||||||
| + | 1 reference(s) hidden. |
| ABB Automation Products GmbH | 2600T Series - Model 266 P-dP | 0101 | Resource |
| Description: | Diagnosis Simulation |
| Size: | 4 |
| Category: | Vendor |
| Access: | Engineer |
| Type: | bit Array |
| Help: | Diagnosis Simulation |
| Enumerations: | 0 – FE Failed 1 – FE Unknown 2 – FE Communication Error 3 – FE NV Failed 5 – CB NV Failure 6 – FE NV Warning 7 – CB NV Warning 8 – Replace Required Both Direction Enabled 9 – Replace Required FE to CB Blocked 10 – Replace FE to CB Blocked 11 – PdP Sensor Failure 12 – SP Sensor Failure 13 – ST Sensor Failure 14 – Overrange 15 – PdP out of Limits 16 – SP out of Limits 17 – ST out of Limits 18 – Max Working Pressure Execeeded 19 – PdP Simulation 20 – SP Simulation 21 – ST Simulation 22 – PV out of High Range 23 – PV out of Low Range 24 – Both Plugged 25 – Plus Plugged 26 – Minus Plugged 27 – One Plugged 28 – Pild Input (Max Deviation) |
| + | 1 reference(s) hidden. |
| Siemens AG | SITRANS P DSIII/P300 FF | 0101 | Resource |
| Description: | Diagnostics Simulation |
| Child(s): | 1 – VALUE 2 – ENABLE |
| Size: | 3 |
| Category: | Vendor |
| Access: | Engineer |
| Type: | Structure |
| Help: | This parameter is used for the simulation of the Diagnostics Errors parameter. |