| Parameters | Units | About | Contact | |||||||||
| + | 1 reference(s) hidden. |
| ABB Automation Products GmbH | TB82PH | 0101 | TB82PH pH, ORP, pION | Transducer |
| Description: | Diagnostics Active |
| Category: | Vendor |
| Access: | Engineer |
| Type: | Enumeration |
| Help: | The diagnostics state allows disabling of the built-in sensor diagnostics. When a sensor does not have a solution ground, such as the ABB Type TB5 sensors, the diagnostic signal cannot be injected into the process liquid. The diagnostics should be disabled for these situations and for applications using very pure water. |
| Enumerations: | 0 – OFF 1 – ON |