SAMSON AG373x-50201Advanced PVTransducer
Description:Trigger edge
Parent:DL_CONFIG_WR
Category:Vendor
Access:Engineer
Type:Enumeration
Help:Start condition for triggered data logger to start at falling below or exceeding the initial value.
Enumerations:0 – Low signal/falling edge/bottom band exit
1 – High signal/rising edge/top band exit
2 – Band exit
3 – Band entry