| Parameters | Units | About | Contact | |||||||||
| + | 1 reference(s) hidden. |
| Emerson Process Management | Fisher DVC6200f / DVC6000f | 0203 | Transducer |
| Description: | Drive Current Alert Point |
| Parent: | INST_ALERTS_CONFIG |
| Minimum Range: | 5 |
| Maximum Range: | 100 |
| Category: | Vendor |
| Access: | Engineer |
| Type: | 32 bit Float |
| Help: | The alert point is the absolute difference between the Drive Current and the Drive Signal and is expressed as a percentage of the Maximum Drive Current. Valid range is 5-100%. |