Foundation Fieldbus Parameter Search (βeta)

"Taking the frustration out of foundation"

Parameters Units About Contact
 
Parameter:
USED_ECHO_TIMEOUT

+1 reference(s) hidden.
Emerson Process ManagementRosemount 5600 TankRadar PRO0201Transducer
Description:Echo timeout
Category:Vendor
Access:Engineer
Type:32 bit Unsigned Integer
Help:Use Echo Timeout to define the time in seconds before the gauge will start to search for a surface echo outside the Close Distance window if it has been lost. If an echo has been lost, the gauge will not start searching or set Invalid Level until this time has elapsed. This value can for instance be increased if the surface temporarily is lost due to i.e. foam or turbulence.