Foundation Fieldbus Parameter Search (βeta)

"Taking the frustration out of foundation"

Parameters Units About Contact
 
Parameter:
+2 reference(s) hidden.
Emerson Process ManagementRosemount 5400 Series0203Transducer
Rosemount 5600 TankRadar PRO0103Transducer
Description:Process Condition
Size:4
Category:Vendor
Access:Engineer
Type:bit Array
Help:To describe the process condition, mark the check boxes that correspond to the conditions in your tank: 1. Rapid level changes. Optimizes the transmitter for measurement conditions where the level changes quickly due to filling and emptying of the tank.2. Turbulent Surface. This parameter may be used if the tank e.g. contains boiling products causing a turbulent surface. By setting this parameter the performance of the transmitter will be improved when there are small and quickly changing amplitudes and levels.3. Foam. Setting this parameter optimizes the transmitter for conditions with weak and varying surface echo amplitudes.4. Solid Products. Solid materials such as cement, grains, pellets, etc. For best performance you should not choose more than two options.
Enumerations:27 – Solid Product
28 – Foam
29 – Turbulent Surface
30 – Reserved
31 – Rapid Changes

+1 reference(s) hidden.
Emerson Process ManagementRosemount 5300 Series0107Transducer
Description:Process Condition
Size:4
Category:Vendor
Access:Engineer
Type:bit Array
Help:Enable checkboxes depending on environment in the tank. Note: For best performance, choose only if applicable and not more than two options.
Enumerations:3 – Rapid Changes

+1 reference(s) hidden.
Emerson Process ManagementRosemount 5600 TankRadar PRO0201Transducer
Description:Process Condition
Size:4
Category:Vendor
Access:Engineer
Type:bit Array
Help:To describe the Process Condition, mark the check boxes that correspond to the conditions in your tank. For best performance you should not choose more than two options.Rapid level changes - Optimizes the transmitter for measurement conditions where the level changes quickly due to filling and emptying of the tank.Turbulent Surface - This parameter may be used if the tank e.g. contains boiling products causing a turbulent surface. By setting this parameter the performance of the transmitter will be improved when there are small and quickly changing amplitudes and levels.Foam - Setting this parameter optimizes the transmitter for conditions with weak and varying surface echo amplitudes.Solid Products - Solid materials such as cement, grains, pellets, etc.
Enumerations:26 – Solid Product
27 – Foam
28 – Turbulent Surface
30 – Rapid Changes