EVENT_LOG_EVENT_TIME_STAMP

+2 reference(s) hidden.
Metso AutomationND9000F0301Transducer
0401Transducer
Category:Vendor
Access:View Only
Type:Enumeration
Help:No Help Available
Enumerations:0 – none
191 – event log initialized
241 – external reset
341 – factory defaults activated
441 – params backup restore
531 – pos calib ok
631 – calib ok
731 – mA inp calib ok
871 – test cancelled
971 – test ok
1071 – test failed
1193 – watchdog reset
1293 – board to board comm fail
1323 – pressure sensor 1 fail
1423 – pressure sensor 2 fail
1523 – pressure sensor 3 fail
1623 – spool valve sensor fail
1723 – temperature sensor fail
1853 – statistics pool fail
1993 – event pool fail
2033 – pos calib fail
2133 – ctrl tune fail
2233 – mA inp calib fail
2343 – factory settings create fail
2443 – factory settings restore fail
2552 – total operation time warning
2652 – valve full strokes warning
2752 – valve reversals warning
2852 – actuator full strokes warning
2952 – actuator reversals warning
3052 – spool valve full strokes warning
3152 – spool valve reversals warning
3252 – steady state deviation warning
3352 – dynamic state deviation warning
3452 – stiction low warning
3552 – stiction high warning
3652 – load for opening low warning
3752 – load for opening high warning
3812 – supply pressure warning
3912 – temperature warning
4012 – hunting detection warning
4114 – deviation alarm
4254 – stiction low alarm
4354 – stiction high alarm
4454 – load for opening low alarm
4554 – load for opening high alarm
4614 – spool valve problem
4714 – pneumatics problem
4814 – friction problem
4995 – continued watchdog reset
5095 – failsafe activated
5125 – position sensor fail
5225 – setpoint sensor fail
5325 – prestage shortcut
5425 – prestage cut
5595 – processor failure
5645 – parameters pool fail
5763 – control params failed
5811 – online fail recovery
5921 – io diagn fail recovery
6093 – ad restart
6150 – statistics saved
6231 – calib cancelled
6333 – pos sensor range error
6433 – calib timeout
6533 – calib start fail
6633 – calib fail
6751 – online alarm recovery
6893 – DAC comm fail
6991 – factory settings created
7091 – flash sect erased
7191 – flash sect erase fail
7254 – fieldbus comm fail rate warning
7333 – spool sensor range error
7490 – database compressed
7562 – emergency control activated
7661 – emergency control deactivated
7723 – prestage coil cut
7852 – relative open stroke warning
7952 – absolute open stroke warning
8052 – relative close stroke warning
8152 – absolute close stroke warning
8252 – open load high warning
8352 – close load high warning
8452 – open load low warning
8552 – close load low warning
8652 – valve open latency warning
8752 – pressure open latency warning
8852 – valve close latency warning
8952 – pressure close latency warning
9052 – pressure open slope warning
9152 – pressure close slope warning
9214 – valve open stuck alarm
9314 – valve close stuck alarm
9414 – valve intermediate stuck alarm
9514 – unnecessary valve movement alarm
9614 – too slow valve opening alarm
9714 – too slow valve closing alarm
9814 – excessive movement in open pos alarm
9914 – deficient movement in open pos alarm
10014 – excessive movement in close pos alarm
10114 – deficient movement in close pos alarm
10231 – pressure calib ok
10331 – ctrl tune ok
10433 – pos pressure range error
10571 – step test failed
10671 – loop test failed
10771 – db test failed
10871 – analysis test failed
10971 – spool step test failed
11071 – spool loop test failed
11171 – spool db test failed
11271 – wc test failed
11371 – step test ok
11471 – loop test ok
11571 – analysis test ok
11671 – spool step test ok
11771 – spool loop test ok
11871 – spool db test ok
11971 – wc test ok
12071 – db test ok
12131 – one point cal ok
12231 – one point cal failed
12331 – calib supply pressure failure
12471 – test supply pressure failure
12511 – online supply pressure recovery
12611 – online temperature recovery
12711 – online deviation recovery
12811 – online hunting detection recovery
12911 – online spool valve problem recovery
13011 – online pneumatics problem recovery
13111 – online friction problem recovery
13212 – too low supply for 1act warning
13311 – online too low supply for 1act recovery
13452 – valve reversals trend warning
13552 – setpoint reversals trend warning
13652 – valve travel trend warning
13752 – valve reversals while ssp trend warning
13852 – load for closing low warning
13952 – load for closing high warning
14054 – load for closing low alarm
14154 – load for closing high alarm
14223 – prestage shortcut
14321 – prestage shortcut recovery
14421 – prestage cut recovery
65535 – any

+1 reference(s) hidden.
Metso AutomationVG9000F0107Transducer
Category:Vendor
Access:View Only
Type:Enumeration
Help:Event log events.
Enumerations:0 – None
191 – Event Log Initialized
241 – External Reset
341 – Factory Defaults Activated
441 – Parameters Backup Restored
531 – Position Calibration Successful
631 – Calibration Successful
731 – mA Input Calibration Successful
871 – Test Cancelled
971 – Test Ok
1071 – Test Failed
1193 – Continued Watchdog Reset
1293 – Fieldbus Communication Failure Rate Limit Exceeded
1323 – Pressure Sensor 1 Failure Detected
1423 – Pressure Sensor 2 Failure Detected
1523 – Pressure Sensor 3 Failure Detected
1623 – Spool Valve Sensor Failure Detected
1723 – Temperature Sensor Failure Detected
1853 – Statistics Database Error Detected
1993 – Event Database Error Detected
2033 – Position Calibration Failed
2133 – Control Tuning Failed
2233 – mA Input Calibration Failed
2343 – Factory Settings Create Failure Detected
2443 – Factory Settings Restore Failure Detected
2552 – Total Operation Time Counter Limit Exceeded
2652 – Valve Full Strokes Counter Limit Exceeded
2752 – Valve Reversals Counter Limit Exceeded
2852 – Actuator Full Strokes Counter Limit Exceeded
2952 – Actuator Reversals Counter Limit Exceeded
3052 – Spool Valve Full Strokes Counter Limit Exceeded
3152 – Spool Valve Reversals Counter Limit Exceeded
3252 – Steady State Deviation Trend Limit Exceeded
3352 – Dynamic State Deviation Trend Limit Exceeded
3452 – Stiction Trend Low Limit Exceeded
3552 – Stiction Trend High Limit Exceeded
3652 – Load For Opening Trend Low Limit Exceeded
3752 – Load For Opening Trend High Limit Exceeded
3812 – Supply Pressure Limit Exceeded
3912 – Temperature Limit Exceeded
4012 – Hunting Detected
4114 – Deviation Detected
4254 – Stiction Low Limit Exceeded
4354 – Stiction High Limit Exceeded
4454 – Load For Opening Low Limit Exceeded
4554 – Load For Opening High Limit Exceeded
4614 – Spool Valve Stuck Detected
4714 – Pneumatics Problem Detected
4814 – Friction Problem Detected
4995 – Continued Watchdog Reset
5095 – Failsafe Active
5125 – Position Sensor Failure Detected
5225 – Setpoint Sensor Failure Detected
5325 – Prestage Shortcut Detected
5425 – Prestage Cut Detected
5595 – Processor Failure Detected
5645 – Parameters Pool Failure Detected
5763 – Control Parameters Failure Detected
5811 – Failure Recovery
5921 – Sensor Failure Recovery
6093 – " "
6150 – Statistics Saved
6231 – Calibration Cancelled
6333 – Position Sensor Range Error Detected
6433 – Calibration Timeout
6533 – Calibration Start Failed
6633 – Calibration Failed
6751 – Limit Recovery
6893 – Position Transmitter Not Activated
6991 – Factory Settings Created
7091 – Flash Sector Erased
7191 – Flash Sector Erase Failure Detected
7254 – Fieldbus Comminucation Failure Rate Limit Exceeded
7333 – Spool Sensor Range Error Detected
7490 – Database Compressed
7562 – Emergency Control Activated
7661 – Emergency Control Deactivated
7723 – Prestage Cut Detected
7852 – Open Stroke Deviation Trend Limit Exceeded
7952 – Too High Total Stroke Time Open Detected
8052 – Close Stroke Deviation Trend Limit Exceeded
8152 – Too High Total Stroke Time Close Detected
8252 – Open Load High Limit Exceeded
8352 – Close Load High Limit Exceeded
8452 – Open Load Low Limit Exceeded
8552 – Close Load Low Limit Exceeded
8652 – Valve Reaction Time Open Exceeded
8752 – Spool Valve Reaction Time Open Exceeded
8852 – Valve Reaction Time Close Exceeded
8952 – Spool Valve Reaction Time Close Exceeded
9052 – Pressure Open Slope Limit Exceeded
9152 – Pressure Close Slope Limit Exceeded
9214 – Valve Open Stuck Detected
9314 – Valve Close Stuck Detected
9414 – Valve Intermediate Stuck Detected
9514 – Unintended Valve Movement Detected
9614 – Too Slow Valve Opening Detected
9714 – Too Slow Valve Closing Detected
9814 – Excessive Movement In Open Position Detected
9914 – Deficient Movement In Open Position Detected
10014 – Excessive Movement In Close Position Detected
10114 – Deficient Movement In Close Position Detected
10231 – Pressure Calibration Successful
10331 – Control Tuning Successful
10433 – Position Pressure Range Error Detected
10571 – Multipoint Step Test Failed
10671 – Dynamic Loop Test Failed
10771 – Valve Deadband Test Failed
10871 – Valve Analysis Test Failed
10971 – Spool Step Test Failed
11071 – Spool Loop Test Failed
11171 – Spool Deadband Test Failed
11271 – " "
11371 – Multipoint Step Test Succcessful
11471 – Dynamic Loop Test Successful
11571 – Valve Analysis Test Successful
11671 – Spool Step Test Successful
11771 – Spool Loop Test Successful
11871 – Spool Deadband Test Successful
11971 – " "
12071 – Valve Deadband Test Successful
12131 – One Point Calibration Successful
12231 – One Point Calibration Failed
12331 – Calibration Supply Pressure Failure Detected
12471 – Test Supply Pressure Failure Detected
12511 – Supply Pressure Back In Limits
12611 – Temperature Back In Limits
12711 – Deviation Problem Recovery
12811 – Hunting Problem Recovery
12911 – Spool Valve Problem Recovery
13011 – Pneumatics Problem Recovery
13111 – Friction Problem Recovery
13212 – Supply Pressure For Single Acting Actuator Low Limit Exceeded
13311 – Supply Pressure For Single Acting Actuator Back In Limits
13452 – Valve Reversals Trend Limit Exceeded
13552 – Setpoint Reversals Trend Limit Exceeded
13652 – Valve Travel Trend Limit Exceeded
13752 – Valve Reversals While Stable Setpoint Trend Limit Exceeded
13852 – Load For Closing Trend Low Limit Exceeded
13952 – Load For Closing Trend High Limit Exceeded
14054 – Load For Closing Low Limit Exceeded
14154 – Load For Closing High Limit Exceeded
14223 – Prestage Shortcut Detected
14321 – Prestage Shortcut Recovery
14421 – Prestage Cut Recovery
14511 – Valve Open Stuck Recovery
14611 – Valve Close Stuck Recovery
14711 – Valve Intermediate Stuck Recovery
14811 – Unallowed Valve Movement Recovery
14911 – Too Slow Valve Opening Recovery
15011 – Too Slow Valve Closing Recovery
15114 – Too Fast Valve Opening Detected
15214 – Too Fast Valve Closing Detected
15311 – Too Fast Valve Opening Recovery
15411 – Too Fast Valve Closing Recovery
15552 – Supply Pressure Trend Limit Exceeded
15652 – Temperature Trend Limit Exceeded
15723 – Position Sensor Failure Detected
15815 – Supply Pressure Limit Exceeded
15916 – Supply Pressure Back In Limits
16091 – Failsafe Recovery
16114 – Control Adaption Problem Detected
16211 – Control Adaption Problem Recovery
16312 – Reduced Performance Activated
16411 – Reduced Performance Deactivated
16512 – Supply Pressure Drop Detected
16611 – Supply Pressure Drop Recovery
16723 – Position Sensor Out Of Range
16820 – Prestage Shortcut Candidate Detected
16971 – Automatic Partial Stroke Test Start Failed
17071 – Self Test Start Failed
17171 – Manual Emergency Trip Test Start Failed
17271 – Automatic Partial Stroke Test Failed
17371 – Self Test Failed
17471 – Manual Emergency Trip Test Failed
17571 – Test Parameterization Failed
17674 – Test Timeout Detected
17714 – Test Overshoot Detected
17814 – Pressure Drop Detected During test
17914 – Valve Position Changed During Pneumatics Test
18071 – Automatic Partial Stroke Test Successful
18171 – Self Test Successful
18271 – Manual Emergency Trip Test Successful
18371 – Automatic Partial Stroke Test Cancelled
18471 – Self Test Cancelled
18571 – Manual Emergency Trip Test Cancelled
18671 – Manual Partial Stroke Test Start Failed
18771 – Manual Partial Stroke Test Failed
18871 – Manual Partial Stroke Test Successful
18971 – Manual Partial Stroke Test Cancelled
19052 – Partial Stroke Test Counter Limit Exceeded
19174 – Emergency Trip Active
19252 – Partial Stroke Test Loadfactor Trend Low Limit Exceeded
19352 – Partial Stroke Test Loadfactor Trend High Limit Exceeded
19452 – Partial Stroke Test Breakaway Pressure Trend Low Limit Exceeded
19552 – Partial Stroke Test Breakaway Pressure Trend High Limit Exceeded
19652 – Emergency Trip Test Loadfactor Trend Low Limit Exceeded
19752 – Emergency Trip Test Loadfactor Trend High Limit Exceeded
19852 – Emergency Trip Test Breakaway Pressure Trend Low Limit Exceeded
19952 – Emergency Trip Test Breakaway Pressure Trend High Limit Exceeded
20052 – Emergency Trip Test Valve Full Stroke Time Open High Limit 20052
20152 – Emergency Trip Test Valve Full Stroke Time Close High Limit20152
20274 – Alarm State Prevents Test
20391 – Device Usage Changed, Reboot required
20471 – Device Test Restricted
20571 – Alarm state reseted
20631 – Pressure calibration failed
20731 – Transmitter calibration successful
20831 – Transmitter calibration failed
20931 – Coil calibration successful
21031 – Coil calibration failed
21171 – Test disabled
21271 – Invalid Test Start Position
21371 – Test Not Allowed in this Device Usage
21471 – Test Control Channel Reservation Failed
21571 – Pneumatics Test failed: no change in cylinder pressures
21631 – Supply pressure level too low to execute calibration
21731 – Calibration tried to start while emergency line is active
21831 – Calibration tried to start while other calibration is running
21931 – Calibration tried to start while device is in ALARM state
22014 – Housing Pressure Limit Exceeded
22111 – Housing Pressure back in limits