Foundation Fieldbus Parameter Search (βeta)

"Taking the frustration out of foundation"

Parameters Units About Contact
 
Parameter:
+1 reference(s) hidden.
Emerson Process ManagementFisher DVC6200f / DVC6000f0203Transducer
Description:Feedback Connection
Parent:BASIC_SETUP
Category:Vendor
Access:Engineer
Type:Enumeration
Help:Select Feedback Connection based on Instrument Family and Valve Style. For the DVC6200f family, choose one of the 'Array' selections. For rotary valves, choose one of the 'R Stem' selections. For sliding stem valves, choose one of the 'S Stem' selections. If the feedback linkage consists of a roller that follows a cam, select 'S Stem Roller Array'.For the DVC6000f family, choose one of the 'Pot' selections. If the feedback linkage consists of a roller that follows a cam, select 'S Stem Roller Pot'.
Enumerations:1 – RShaft Pot
2 – SStem Roller Pot
3 – SStem Pot
64 – SStem #19 Array
65 – SStem #25 Array
66 – SStem #38 Array
67 – SStem #50 Array
70 – SStem #100 Array
74 – SStem #200 Array
85 – SStem #1 Roller Array
90 – RShaft End Array
95 – RShaft #1 Window Array
97 – RShaft #2 Window Array
100 – Default Array