| Parameters | Units | About | Contact | |||||||||
| + | 1 reference(s) hidden. |
| Emerson Process Management | Fisher DVC6200f / DVC6000f | 0203 | Transducer |
| Description: | Feedback Connection |
| Parent: | BASIC_SETUP |
| Category: | Vendor |
| Access: | Engineer |
| Type: | Enumeration |
| Help: | Select Feedback Connection based on Instrument Family and Valve Style. For the DVC6200f family, choose one of the 'Array' selections. For rotary valves, choose one of the 'R Stem' selections. For sliding stem valves, choose one of the 'S Stem' selections. If the feedback linkage consists of a roller that follows a cam, select 'S Stem Roller Array'.For the DVC6000f family, choose one of the 'Pot' selections. If the feedback linkage consists of a roller that follows a cam, select 'S Stem Roller Pot'. |
| Enumerations: | 1 – RShaft Pot 2 – SStem Roller Pot 3 – SStem Pot 64 – SStem #19 Array 65 – SStem #25 Array 66 – SStem #38 Array 67 – SStem #50 Array 70 – SStem #100 Array 74 – SStem #200 Array 85 – SStem #1 Roller Array 90 – RShaft End Array 95 – RShaft #1 Window Array 97 – RShaft #2 Window Array 100 – Default Array |