| Description: | Flow Spike Filter Percent Window Length |
| Parent: | FLOW_SPIKE_FILTER |
| Category: | Vendor |
| Access: | Engineer |
| Type: | 8 bit Unsigned Integer |
| Help: | After 'Percent Len' measurements with good quality have been displayed a new measurement with good quality is deemed valid and displayed when the difference between the maximum and minimum of the present measurement and ('Percent Len' - 1) previous consecutive measurements is less than the measurement range (default of 27fps for Flow) times ('Percent' / 100). |