Foundation Fieldbus Parameter Search (βeta)

"Taking the frustration out of foundation"

Parameters Units About Contact
 
Parameter:
FINAL_VALUE_CUTOFF_HI_ON

+2 reference(s) hidden.
Flowserve CorporationLOGIX 3400IQ/14000501Flowserve Valve PositionerTransducer
Logix 3400MD0102MainTransducer
Description:Final Pos'n High Cutoff
Minimum Range:FINAL_VALUE_RANGE.EU_0
Maximum Range:FINAL_VALUE_RANGE.EU_100
Category:Vendor
Access:Engineer
Type:32 bit Float
Help:If FINAL_VALUE (positioner's set point) goes above this value the positioner will drive the valve open. FINAL_VALUE must be less than FINAL_VALUE_CUTOFF_HI by more than 1% before the positioner will start to close the valve.

+2 reference(s) hidden.
Metso AutomationND9000F0301Transducer
0401Transducer
Description:Final Pos'n High Cutoff
Category:Vendor
Access:Engineer
Type:32 bit Float
Help:If the FINAL_VALUE is more positive than this value, the valve is forced to its maximum high value (calibrated 100 %).

+1 reference(s) hidden.
Emerson Process ManagementFisher DVC6200f / DVC6000f0203Transducer
Description:Final Pos'n High Cutoff
Minimum Range:FINAL_VALUE_RANGE.EU_0
Maximum Range:FINAL_VALUE_RANGE.EU_100
Category:Standard
Access:Engineer
Type:32 bit Float
Help:Travel Cutoff Hi defines the high cutoff point for the travel in percent (%) of pre-characterized setpoint. Above this cutoff, the travel target is set to 123%. Travel Cutoff Hi is deactivated by setting it to 125.0%.

+1 reference(s) hidden.
SAMSON AG373x-50201Advanced PVTransducer
Description:Final Pos'n High Cutoff
Unit:FINAL_VALUE_RANGE.UNITS_INDEX
Minimum Range:FINAL_VALUE_RANGE.EU_0
Maximum Range:FINAL_VALUE_RANGE.EU_100
Category:Standard
Access:Engineer
Type:32 bit Float
Help:If the FINAL_VALUE is more positive than this value, the value is forced to its maximum high value (fully opened).

+1 reference(s) hidden.
Yamatake CorporationSVP3000 AVP203/AVP3030101AVP Analog OutputTransducer
Description:Final Pos'n High Cutoff
Minimum Range:FINAL_VALUE_RANGE.EU_0
Maximum Range:FINAL_VALUE_RANGE.EU_100
Category:Vendor
Access:Engineer
Type:32 bit Float
Help:when this value exceeded,the valve id forced to its maximum high value.