| Flowserve Corporation | LOGIX 3400IQ/1400 | 0501 | Flowserve Valve Positioner | Transducer |
| Logix 3400MD | 0102 | Main | Transducer |
| Description: | Final Pos'n Low Cutoff |
| Minimum Range: | FINAL_VALUE_RANGE.EU_0 |
| Maximum Range: | FINAL_VALUE_RANGE.EU_100 |
| Category: | Vendor |
| Access: | Engineer |
| Type: | 32 bit Float |
| Help: | If FINAL_VALUE (positioner's set point) goes below this value the positioner will drive the valve closed. FINAL_VALUE must be greater than FINAL_VALUE_CUTOFF_LO by more than 1% before the positioner will start to open the valve. |
| + | 2 reference(s) hidden. |
| Metso Automation | ND9000F | 0301 | Transducer | |
| 0401 | Transducer |
| Description: | Final Pos'n Low Cutoff |
| Category: | Vendor |
| Access: | Engineer |
| Type: | 32 bit Float |
| Help: | If the FINAL_VALUE is more negative than this value (default 2%), the valve is forced to its maximum low value (fully closed against mechanical limit). |
| + | 1 reference(s) hidden. |
| Emerson Process Management | Fisher DVC6200f / DVC6000f | 0203 | Transducer |
| Description: | Final Pos'n Low Cutoff |
| Minimum Range: | FINAL_VALUE_RANGE.EU_0 |
| Maximum Range: | FINAL_VALUE_RANGE.EU_100 |
| Category: | Standard |
| Access: | Engineer |
| Type: | 32 bit Float |
| Help: | Travel Cutoff Lo defines the low cutoff point for the travel in percent (%) of pre-characterized setpoint. Below this cutoff, the travel target is set to -23%. A Travel Cutoff Lo of 0.5% is recommended to help ensure maximum shutoff seat loading. Travel Cutoff Lo is deactivated by setting it to -25.0%. |
| + | 1 reference(s) hidden. |
| SAMSON AG | 373x-5 | 0201 | Advanced PV | Transducer |
| Description: | Final Pos'n Low Cutoff |
| Unit: | FINAL_VALUE_RANGE.UNITS_INDEX |
| Minimum Range: | FINAL_VALUE_RANGE.EU_0 |
| Maximum Range: | FINAL_VALUE_RANGE.EU_100 |
| Category: | Standard |
| Access: | Engineer |
| Type: | 32 bit Float |
| Help: | If the FINAL_VALUE is more negative than this value, the value is forced to its maximum low value (fully closed). |
| + | 1 reference(s) hidden. |
| Yamatake Corporation | SVP3000 AVP203/AVP303 | 0101 | AVP Analog Output | Transducer |
| Description: | Final Pos'n Low Cutoff |
| Minimum Range: | FINAL_VALUE_RANGE.EU_0 |
| Maximum Range: | FINAL_VALUE_RANGE.EU_100 |
| Category: | Vendor |
| Access: | Engineer |
| Type: | 32 bit Float |
| Help: | when this value exceeded,the valve id forced to its minimum low value. |