Foundation Fieldbus Parameter Search (βeta)

"Taking the frustration out of foundation"

Parameters Units About Contact
 
Parameter:
+1 reference(s) hidden.
Berthold Technologies GmbH & Co. KGUniprobe LB490/10101FlowTransducer
Parent:FL_INTERFERENCE_DETECTION
Minimum Range:3
Maximum Range:10
Category:Vendor
Access:Engineer
Type:32 bit Float
Help:Enter the Sigma limit to trigger the radiation interference. The measurement stops as soon as the pulse rate of the Sigma limit value has been reached. The Sigma value should be at least 5. The higher the value, the higher the response threshold. If radiation interference is detected, the measurement stops and the measured value is halted. The measurement continues after 20s if no new radiation interference takes place.