Foundation Fieldbus Parameter Search (βeta)

"Taking the frustration out of foundation"

Parameters Units About Contact
 
Parameter:
+1 reference(s) hidden.
CiDRA Corporate Services, Inc.SONARtrac0201SonarTransducer
Description:Flow Vel Search Limit High
Parent:FLOW_ALGORITHM
Category:Vendor
Access:Engineer
Type:32 bit Float
Help:Define high end of velocity search range to use for determining flow velocity. Defined by: Velocity_Max = (FREQ_MIN * Sensor Spacing) / VF_SEARCH_LIMIT_HIGH. Example: at 10ft/sec, (10 ft/sec*0.3) / 0.2 = 15Hz then (15Hz * 0.2) / 0.15 = 20 ft/sec. This defines the start ft/sec search point for the actual flow velocity peak. Must be set less than value for VF_NYQUIST_LOW.