Parameter:
+2 reference(s) hidden.
Emerson Process ManagementRosemount 5400 Series0203Transducer
Rosemount 5600 TankRadar PRO0103Transducer
Description:Distance Offset (G)
Unit:RADAR_LEVEL_RANGE.UNITS_INDEX
Category:Vendor
Access:Engineer
Type:32 bit Float
Help:The Distance Offset (G) is defined as the distance between the upper reference point and the flange (the flange is referred to as the Transmitters Reference Point). You can use Distance Offset to specify your own reference point at the top of the tank. Set Distance Offset=0 if you want the transmitter's flange as upper reference point. Distance Offset is defined as positive if you use an upper reference point above the Transmitters Reference Point.

+1 reference(s) hidden.
Emerson Process ManagementRosemount 5600 TankRadar PRO0201Transducer
Description:Distance Offset (G)
Unit:RADAR_LEVEL_RANGE.UNITS_INDEX
Category:Vendor
Access:Engineer
Type:32 bit Float
Help:Use the Distance Offset (G) if a reference point other than the lower side of the device flange is required/preferred. The Distance Offset is defined as the distance between the upper reference point and the lower side of the device flange.Enter a positive Distance Offset if a point above the device flange should be used as upper reference point. If the Distance Offset is zero the lower side of the device flange is used as the upper reference point.The Distance Offset is used when the measured level by the device should correspond to the level value obtained by hand-dipping from a hand-dip hatch. In this case the hand-dip hatch is the upper reference point.