Emerson Process ManagementRosemount 5400 Series0203Transducer
Rosemount 5600 TankRadar PRO0103Transducer
0201Transducer
Description:Minimum Level Offset (C)
Unit:RADAR_LEVEL_RANGE.UNITS_INDEX
Category:Vendor
Access:Engineer
Type:32 bit Float
Help:The Minimum Level Offset (C) defines a lower null zone which extends the measurement range beyond the Zero Level Reference Point down to the tank bottom.The Minimum Level Offset is defined as the distance between the zero level (Tank Level Reference Point) and the minimum accepted level, i.e. the tank bottom. Set Minimum Level Offset=0 if you use the tank bottom as zero level reference point. Note that Minimum Level Offset can not be negative.