| Parameters | Units | About | Contact | |||||||||
| + | 1 reference(s) hidden. |
| Siemens AG | SIPART PS2 FF | 0101 | Analog Output | Transducer |
| Description: | Short step zone 'DOWN' |
| Parent: | INIT_VALUES |
| Category: | Vendor |
| Access: | Engineer |
| Type: | 16 bit Integer |
| Help: | This value indicates the current short step zone of the positioner for the down direction. The short step zone is the range of the positioner in which pulse-type control signals are output. The pulse length is proportional to the system deviation. If the system deviation is outside the short step zone, the valves are controlled with maintained contact. |