Foundation Fieldbus Parameter Search (βeta)

"Taking the frustration out of foundation"

Parameters Units About Contact
 
Parameter:
+1 reference(s) hidden.
ABB Automation Products GmbH2600T Series 267/2690201PressureTransducer
Description:ADC Integration time
Minimum Range:1
Maximum Range:13
Category:Vendor
Access:Engineer
Type:8 bit Unsigned Integer
Help:The integration time constant determines the integration time of the incoming main pressure value from the A/D converter at the input of the transmitter's electronic unit. It may be adjusted between 0.1s and 1.3 sec in 100ms steps. A high integration time means that the transmitter operates with its full accuracy and at a unit jump has completely reached the final value after 1.3 s.