Foundation Fieldbus Parameter Search (βeta)

"Taking the frustration out of foundation"

Parameters Units About Contact
 
Parameter:
+26 reference(s) hidden.
ABB Automation Products GmbH2600T Series - Model 266 P-dP0101Input SelectorFunction
BEKA Associates Ltd.BA488CF Series0202Input SelectorFunction
Dresser Valve DivisionFVP (Software Download)0301Input SelectorFunction
Emerson Process ManagementFisher DVC6200f / DVC6000f0203Input SelectorFunction
Rosemount 30511707Input SelectorFunction
Rosemount 3095 MultiVariable Transmitter0103Input SelectorFunction
Rosemount 3144P0105Input SelectorFunction
Rosemount 5300 Series0107Input SelectorFunction
Rosemount 5400 Series0201Input SelectorFunction
0203Input SelectorFunction
Rosemount 848T0601Input SelectorFunction
Endress+HauserPROline Promag 53/550401Input SelectorFunction
PROline Promass 830401Input SelectorFunction
Flowserve CorporationLogix 3400MD0102Input SelectorFunction
Fuji Electric CorporationFCX-AIII Series0101Input SelectorFunction
Metroval Controle de Fluidos Ltda.TDM-FF-010101Input SelectorFunction
Metso AutomationND9000F0301Input SelectorFunction
0401Input SelectorFunction
MTL Instruments9331-T10101Input SelectorFunction
SAMSON AG373x-50201Input SelectorFunction
Yokogawa Electric CorporationEJX0303Input SelectorFunction
YVP (Software Download)0301Input SelectorFunction
Description:Min. Num. of Good Inputs
Minimum Range:0
Maximum Range:10
Category:Standard
Access:Engineer
Type:8 bit Unsigned Integer
Help:If the number of inputs which are good is less than the value of MIN_GOOD then set the out status to bad.

+4 reference(s) hidden.
Metroval Controle de Fluidos Ltda.CMM-010101Input SelectorFunction
Smar International Co.FB7000407Input SelectorFunction
IF3020407Input SelectorFunction
LD2920407Input SelectorFunction
Description:Min. Num. of Good Inputs
Minimum Range:0
Maximum Range:4
Category:Vendor
Access:Engineer
Type:8 bit Unsigned Integer
Help:If the number of inputs which are good is less than the value of MIN_GOOD then set out status to bad.

+3 reference(s) hidden.
Endress+HauserLevelflex M0303Input SelectorFunction
Micropilot M0303Input SelectorFunction
Prosonic M0303Input SelectorFunction
Description:Min. Num. of Good Inputs
Minimum Range:0
Maximum Range:4
Category:Vendor
Access:Engineer
Type:8 bit Unsigned Integer
Help:Determines the minimum number of good inputs for the selector to process.

+1 reference(s) hidden.
Emerson Process ManagementRosemount 20510101Input SelectorFunction
Description:Min. Num. of Good Inputs
Minimum Range:0
Maximum Range:4
Category:Vendor
Access:Engineer
Type:8 bit Unsigned Integer
Help:If the number of inputs which are good is less than this value, then the output status is set to bad.

+1 reference(s) hidden.
FoxboroIASPT101701Input SelectorFunction
Description:Min. Num. of Good Inputs
Category:Vendor
Access:Engineer
Type:Enumeration
Help:If the number of inputs which are good is less than the value of MIN_GOOD then set the out status to bad
Enumerations:0 – Uninitialized
1 – One Good
2 – Two Good
3 – Three Good
4 – Four Good