Foundation Fieldbus Parameter Search (βeta)

"Taking the frustration out of foundation"

Parameters Units About Contact
 
Parameter:
+1 reference(s) hidden.
MTL InstrumentsF809F0201DiscreteTransducer
Description:Module temperature high-high alert
Parent:MODULE_TEMP_HIGH_LIMITS
Category:Vendor
Access:Engineer
Type:16 bit Unsigned Integer
Help:The default values are limits for the F801 fieldbus power supply maximum operating temperature of 65° C. The user may reset this to the maximum operating temperature of the power supply used or select a lower limit based on normal operating temperature of the cabinet. Setting the limit at the lower of the maximum operating temperature of the power supply or 10°C above the normal operating temperature is recommended