| Parameters | Units | About | Contact | |||||||||
| + | 1 reference(s) hidden. |
| MTL Instruments | F809F | 0102 | Discrete | Transducer |
| Description: | Module temperature high alert |
| Category: | Vendor |
| Access: | Engineer |
| Type: | 16 bit Unsigned Integer |
| Help: | The default values are limits for the F801 fieldbus power supply maximum operating temperature of 65° C. The user may reset this to the maximum operating temperature of the power supply used or select a lower limit based on normal operating temperature of the cabinet. Setting the limit at the lower of the maximum operating temperature of the power supply or 10°C above the normal operating temperature is recommended |
| + | 1 reference(s) hidden. |
| MTL Instruments | F809F | 0201 | Discrete | Transducer |
| Description: | Module temperature high alert |
| Parent: | MODULE_TEMP_HIGH_LIMITS |
| Category: | Vendor |
| Access: | Engineer |
| Type: | 16 bit Unsigned Integer |
| Help: | The default values are limits for the F801 fieldbus power supply maximum operating temperature of 65° C. The user may reset this to the maximum operating temperature of the power supply used or select a lower limit based on normal operating temperature of the cabinet. Setting the limit at the lower of the maximum operating temperature of the power supply or 10°C above the normal operating temperature is recommended |