MODULE_TEMP_HIGH_HIGH_LIMIT MODULE_TEMP_HIGH_LIMIT

+1 reference(s) hidden.
MTL InstrumentsF809F0201DiscreteTransducer
Description:Module temperature high limits
Child(s):1 – MODULE_TEMP_HIGH_HIGH_LIMIT
2 – MODULE_TEMP_HIGH_LIMIT
Size:4
Category:Vendor
Access:Engineer
Type:Structure
Help:The default values are limits for the F801 fieldbus power supply maximum operating temperature of 65°C. The user may reset this to the maximum operating temperature of the power supply used or select a lower limit based on normal operating temperature of the cabinet. Setting the limit at the lower of the maximum operating temperature of the power supply or 10°C above the normal operating temperature is recommended