Foundation Fieldbus Parameter Search (βeta)

"Taking the frustration out of foundation"

Parameters Units About Contact
 
Parameter:
+1 reference(s) hidden.
MTL InstrumentsF809F0201DiscreteTransducer
Description:Reset Retransmit Counters
Maximum Range:999
Category:Vendor
Access:Engineer
Type:16 bit Unsigned Integer
Help:Parameter used to delete selected retransmission counters in systems not supporting methods.Input number in the format SDD. S = Segment number from 1 to 8. DD = device number from 01 to 32.For example writing 108 will reset counter for device 8 on segment 1. Writing S00 will reset all counters for all devices and segment totals on segment S. Writing 000 will reset all counters for all devices and segment totals on all segments. The default value for this parameter is 999 to prevent risk of data being reset accidentally