Foundation Fieldbus Parameter Search (βeta)

"Taking the frustration out of foundation"

Parameters Units About Contact
 
Parameter:
+3 reference(s) hidden.
Metso AutomationND9000F0301Transducer
0401Transducer
VG9000F0107Transducer
Category:Vendor
Access:Engineer
Type:Enumeration
Help:Initiation of a self-calibration-procedure.
Enumerations:0 – Idle
2 – Start automatic travel calibration and position control tuning
100 – Start automatic travel calibration
101 – Start position control tuning
110 – Start single point calibration
255 – Cancel current calibration procedure

+1 reference(s) hidden.
ABB Automation Products GmbHTZID-C120/2200101Transducer
Description:Selfcalibration Command
Category:Vendor
Access:Engineer
Type:Enumeration
Enumerations:0 – Select Item
1 – Start
2 – Stop / Cancel

+1 reference(s) hidden.
Flowserve CorporationPMV D30101Analog OutputTransducer
Description:Self calibration
Category:Vendor
Access:Engineer
Type:Enumeration
Help:The unit has to be out of service. Set correct actuator function, actuator size, direction and valve type befor start calibration
Enumerations:0 – No Function
1 – Auto Calibration START
2 – Travel Calibration START
255 – Abort Calibration

+1 reference(s) hidden.
Foxboro-EckardtSRD 9600902Flowserve Valve PositionerTransducer
Category:Vendor
Access:Engineer
Type:Enumeration
Help:Self calibration commands. You can select an Autostart procedure which will automatically determine the valve end positions and control parameters. Resetting Travel sum and Cycle Counter is also available here.
Enumerations:0 – Initial value
2 – Autostart
3 – Short Autostart
7 – Reset Travel Sum/Cycle Count to ZERO