Foundation Fieldbus Parameter Search (βeta)

"Taking the frustration out of foundation"

Parameters Units About Contact
 
Parameter:
+1 reference(s) hidden.
Emerson Process ManagementFisher DVC6200f / DVC6000f0203Transducer
Description:Shutdown Trigger
Parent:INST_ALERTS_CONFIG
Size:4
Category:Vendor
Access:Engineer
Type:bit Array
Help:Enables Self Test Shutdown. When enabled and the alert condition is present, the transducer Actual mode is placed Out of Service. The instrument will attempt to drive the valve to the Zero Power Condition and will no longer execute transducer control function.
Enumerations:0 – Drive Current Shutdown
1 – Program Memory Shutdown
2 – Static Memory Shutdown
3 – I/O Processor Shutdown
4 – Travel Sensor Shutdown
5 – Pressure A Sensor Shutdown
6 – Output Block Timeout Shutdown