DECIMAL EU_0 EU_100 INTERFACE_SIGNAL_STRENGTH RADAR_LEVEL_SIGNAL_STRENGTH RADAR_LEVEL_SIGNAL_STRENGTH_RANGE STATUS UNITS_INDEX VALUE

+2 reference(s) hidden.
Emerson Process ManagementRosemount 88000701Transducer
0901Transducer
Description:Signal Strength
Category:Vendor
Access:View Only
Type:32 bit Float
Help:The Signal Strength is the ratio of the signal strength to the trigger level. The Signal Strength should be greater than 4.0 under normal flowing conditions. Low Signal Strength level can be caused by: Improper configuration. Improper setting of signal processing. Failing sensor. Cavitation. Blocked meter body. If the Signal Strength is less than 4.0 under normal flowing conditions: Check the configuration to ensure that it is configured properly. Check the signal processing parameters and/or perform an 'optimize flow range'. Check the impedance of the sensor using the procedure from the manual. Verify that cavitation is not occurring. Consult the manual for further troubleshooting.